Custom Electronics Systems, Inc.
455 FORUM PARKWAY RURAL HALL, NORTH CAROLINA
27045
PHONE: (336) 969 2411 FAX: 336 969 2412
EMAIL: INFO@DRAFTRANGE.COM
CES 492 Specifications
Hysteresis and Repeatability: +.05%
Non-linearity: +.5% BFSL Max.
Pressure Range (.1 to 25"H2 0)
Overpressure: 1 PSI HI Side , .5 PSI low side
Line Pressure: 10 PSIA Max.
Operating Temperature:0 to 60 0 C
Thermal Zero Shift:+.08%/ 0 C
Thermal Span Shift:+.08%/ 0 C
Channel Matching:+.1% max.
Accuracy+.5 % over full range
Overpressure:1 PSI HI Side .5 PSI low side
Line Pressure: 10 PSIA Max.
Delta Range: 0-20% of Full Flow
Output :4-20 mA into 1000 ohms
0-10 volts into 2000 ohms
Flow Monitor:0-5 volts
Termination:
Electrical: Plug in captive screw type
Pneumatic: 1/8" barb
Power Requirements:120 VAC @ 1VA
or 24 VDC @ 100 mA
Enclosure: see dimensions
Specification subject to change without notice
ORDERING INFORMATION
ORDERING INFORMATION:
CES 492 1 -2-3-4-5-6-7
1. POWER:
A:24 VDC
B: 120 VAC
2. A SPAN Specify the maximum full scale
3 .B SPAN pressure for each channel
4. CONTROLLER OUTPUT
I: 4-20 mA
V: 0-10 volts
5. ACTION
I: indirect
D: Direct
6. DELTA
A: B tracks > A
B: B tracks < A
7. OPTIONAL DISPLAY Specify the desired zero and span readings
PINOUT
1. Gnd
2. Flow A
3. Flow B
4. Output
5. +24 VDC
6. Delta
7. AC Neutral
8. AC Hot
APPLICATION NOTES:
DIMENSIONS:
 |